Colten C.

Colten C. Job Checkin

Performed comprehensive annual maintenance on a Lennox furnace system. Conducted full component inspection with all parts functioning properly and system operating within normal parameters. Replaced air filter and verified proper operation; no issues identified at this time.

Performed comprehensive annual maintenance on a Lennox furnace system. Conducted full component inspection with all parts functioning properly and system operating within normal parameters. Replaced air filter and verified proper operation; no issues identified at this time. Performed comprehensive annual maintenance on a Lennox furnace system. Conducted full component inspection with all parts functioning properly and system operating within normal parameters. Replaced air filter and verified proper operation; no issues identified at this time.

Dan S.

Dan S. Job Checkin

Responded to customer complaint regarding gas burner ignition failure on outdoor wood/gas central boiler system. Diagnostic inspection revealed proper burner starting sequence but insufficient gas pressure. Determined that customer's 100lb LP tank with low-pressure regulator cannot provide adequate pressure through the underground line. Advised customer to upgrade to minimum 250-gallon LP tank with appropriate regulators to resolve the issue.

Responded to customer complaint regarding gas burner ignition failure on outdoor wood/gas central boiler system. Diagnostic inspection revealed proper burner starting sequence but insufficient gas pressure. Determined that customer's 100lb LP tank with low-pressure regulator cannot provide adequate pressure through the underground line. Advised customer to upgrade to minimum 250-gallon LP tank with appropriate regulators to resolve the issue. Responded to customer complaint regarding gas burner ignition failure on outdoor wood/gas central boiler system. Diagnostic inspection revealed proper burner starting sequence but insufficient gas pressure. Determined that customer's 100lb LP tank with low-pressure regulator cannot provide adequate pressure through the underground line. Advised customer to upgrade to minimum 250-gallon LP tank with appropriate regulators to resolve the issue.

Ethan S.

Ethan S. Job Checkin

Performed scheduled furnace maintenance on 3-year-old FRP unit. Replaced dirty filter, inspected and verified clean blower assembly, tested all electrical components, and confirmed heat exchanger integrity. System operating within specifications with proper 60°F temperature rise and correct gas pressure. Verified proper venting with exterior PVC pipes clear during winter conditions.

Performed scheduled furnace maintenance on 3-year-old FRP unit. Replaced dirty filter, inspected and verified clean blower assembly, tested all electrical components, and confirmed heat exchanger integrity. System operating within specifications with proper 60°F temperature rise and correct gas pressure. Verified proper venting with exterior PVC pipes clear during winter conditions.

Cody S.

Cody S. Job Checkin

Responded to emergency call for leaking pipe. Diagnosed a hole in the pressure switch plate causing water to gush when well pump activated. Replaced the defective 40/60 pressure switch with a new unit, restoring proper function to the residential water system.

Responded to emergency call for leaking pipe. Diagnosed a hole in the pressure switch plate causing water to gush when well pump activated. Replaced the defective 40/60 pressure switch with a new unit, restoring proper function to the residential water system. Responded to emergency call for leaking pipe. Diagnosed a hole in the pressure switch plate causing water to gush when well pump activated. Replaced the defective 40/60 pressure switch with a new unit, restoring proper function to the residential water system.

Trent L.

Trent L. Job Checkin

Diagnosed 10+ year old natural gas furnace exhibiting no-heat condition. Investigation revealed system was displaying pressure switch code, but all pressure switch hoses were clear. Determined root cause was empty propane tank resulting in no gas supply to furnace. Powered down system to prevent continuous ignition attempts; advised customer to restore power after refilling propane and recommended regular tank level monitoring.

Diagnosed 10+ year old natural gas furnace exhibiting no-heat condition. Investigation revealed system was displaying pressure switch code, but all pressure switch hoses were clear. Determined root cause was empty propane tank resulting in no gas supply to furnace. Powered down system to prevent continuous ignition attempts; advised customer to restore power after refilling propane and recommended regular tank level monitoring.

Mike B.

Mike B. Job Checkin

Completed comprehensive heating system maintenance across multiple areas. Addressed low water in parlor boilers, replaced defective slab sensor at parlor entry, cleaned accumulated nesting debris from two LB white heaters in half bar, and restored them to operational condition. Documented pin-hole leak in expansion tank that customer elected to monitor rather than immediately repair.

Completed comprehensive heating system maintenance across multiple areas. Addressed low water in parlor boilers, replaced defective slab sensor at parlor entry, cleaned accumulated nesting debris from two LB white heaters in half bar, and restored them to operational condition. Documented pin-hole leak in expansion tank that customer elected to monitor rather than immediately repair.

Beca R.

Beca R. Job Checkin

Performed diagnostic on 16-year-old heating system that was blowing cold air intermittently after resets. Inspection revealed improper combustion and upon removal of blower assembly, discovered water accumulation, darkening, evidence of rodent intrusion, and completely failed secondary heat exchanger. Equipment was tagged unsafe for operation and replacement options were provided to customer.

Performed diagnostic on 16-year-old heating system that was blowing cold air intermittently after resets. Inspection revealed improper combustion and upon removal of blower assembly, discovered water accumulation, darkening, evidence of rodent intrusion, and completely failed secondary heat exchanger. Equipment was tagged unsafe for operation and replacement options were provided to customer. Performed diagnostic on 16-year-old heating system that was blowing cold air intermittently after resets. Inspection revealed improper combustion and upon removal of blower assembly, discovered water accumulation, darkening, evidence of rodent intrusion, and completely failed secondary heat exchanger. Equipment was tagged unsafe for operation and replacement options were provided to customer.

Mike B.

Mike B. Job Checkin

Responded to no-heat call for a barn boiler system. Diagnosed low water level in the aging boiler and replenished system water to restore operation. Unit is showing significant deterioration with corrosion on copper piping connections. Recommended replacement options to owner, including commercial water heater and unit heater installations, with estimates to follow.

Responded to no-heat call for a barn boiler system. Diagnosed low water level in the aging boiler and replenished system water to restore operation. Unit is showing significant deterioration with corrosion on copper piping connections. Recommended replacement options to owner, including commercial water heater and unit heater installations, with estimates to follow. Responded to no-heat call for a barn boiler system. Diagnosed low water level in the aging boiler and replenished system water to restore operation. Unit is showing significant deterioration with corrosion on copper piping connections. Recommended replacement options to owner, including commercial water heater and unit heater installations, with estimates to follow.

Nick J.

Nick J. Job Checkin

Replaced incorrectly supplied LP water heater with appropriate natural gas model after customer reported no hot water. Original unit had been installed by third party approximately one month prior. Verified proper installation of new water heater with all gas, water, and vent connections secured and functioning correctly.

Replaced incorrectly supplied LP water heater with appropriate natural gas model after customer reported no hot water. Original unit had been installed by third party approximately one month prior. Verified proper installation of new water heater with all gas, water, and vent connections secured and functioning correctly. Replaced incorrectly supplied LP water heater with appropriate natural gas model after customer reported no hot water. Original unit had been installed by third party approximately one month prior. Verified proper installation of new water heater with all gas, water, and vent connections secured and functioning correctly.

Beca R.

Beca R. Job Checkin

Performed comprehensive furnace tune-up on aging system for new homeowner. Discovered significant dirt accumulation on blower wheel requiring thorough cleaning. Identified deteriorating ductwork with direct exterior opening that needed replacement to restore proper system functionality and efficiency.

Performed comprehensive furnace tune-up on aging system for new homeowner. Discovered significant dirt accumulation on blower wheel requiring thorough cleaning. Identified deteriorating ductwork with direct exterior opening that needed replacement to restore proper system functionality and efficiency. Performed comprehensive furnace tune-up on aging system for new homeowner. Discovered significant dirt accumulation on blower wheel requiring thorough cleaning. Identified deteriorating ductwork with direct exterior opening that needed replacement to restore proper system functionality and efficiency.

Gary L.

Gary L. Job Checkin

Performed routine maintenance tune-up on 20-year-old Lennox high-efficiency furnace. Inspected heat exchanger (good condition) and verified proper combustion. Identified corrosion on condensation trap indicating possible crack requiring replacement. System currently functioning correctly but recommended condensation trap replacement and consultation with comfort advisor for long-term reliability.

Performed routine maintenance tune-up on 20-year-old Lennox high-efficiency furnace. Inspected heat exchanger (good condition) and verified proper combustion. Identified corrosion on condensation trap indicating possible crack requiring replacement. System currently functioning correctly but recommended condensation trap replacement and consultation with comfort advisor for long-term reliability. Performed routine maintenance tune-up on 20-year-old Lennox high-efficiency furnace. Inspected heat exchanger (good condition) and verified proper combustion. Identified corrosion on condensation trap indicating possible crack requiring replacement. System currently functioning correctly but recommended condensation trap replacement and consultation with comfort advisor for long-term reliability.

Ben W.

Ben W. Job Checkin

Evaluated ongoing dehumidifier installation issues in basement where customer expressed concerns about restricted access to mechanical/laundry room area. Documented current installation configuration showing dehumidifier placement and 10-inch round ductwork connection to return that blocks doorway. Assessed options for repositioning dehumidifier adjacent to furnace, which would require reworking ductwork and drain line to improve accessibility while maintaining proper system function.

Evaluated ongoing dehumidifier installation issues in basement where customer expressed concerns about restricted access to mechanical/laundry room area. Documented current installation configuration showing dehumidifier placement and 10-inch round ductwork connection to return that blocks doorway. Assessed options for repositioning dehumidifier adjacent to furnace, which would require reworking ductwork and drain line to improve accessibility while maintaining proper system function. Evaluated ongoing dehumidifier installation issues in basement where customer expressed concerns about restricted access to mechanical/laundry room area. Documented current installation configuration showing dehumidifier placement and 10-inch round ductwork connection to return that blocks doorway. Assessed options for repositioning dehumidifier adjacent to furnace, which would require reworking ductwork and drain line to improve accessibility while maintaining proper system function.

Dan S.

Dan S. Job Checkin

Diagnosed furnace failure caused by broken intake elbows in the attic that allowed insulation to be drawn into the burner box, preventing ignition. Cleaned all plugged burner components and orifices, temporarily disconnected the intake to allow room air usage, and taped off the intake end to prevent further insulation ingestion. Requested installation crew return to properly re-vent the system.

Diagnosed furnace failure caused by broken intake elbows in the attic that allowed insulation to be drawn into the burner box, preventing ignition. Cleaned all plugged burner components and orifices, temporarily disconnected the intake to allow room air usage, and taped off the intake end to prevent further insulation ingestion. Requested installation crew return to properly re-vent the system. Diagnosed furnace failure caused by broken intake elbows in the attic that allowed insulation to be drawn into the burner box, preventing ignition. Cleaned all plugged burner components and orifices, temporarily disconnected the intake to allow room air usage, and taped off the intake end to prevent further insulation ingestion. Requested installation crew return to properly re-vent the system.

Mike B.

Mike B. Job Checkin

Responded to a no heat emergency for a 20-year-old Amana LP furnace that was blowing cold air and running constantly. Discovered tripped rollout switch. Performed thorough inspection of heat exchanger but could not definitively locate compromise despite checking through blower access and top of unit. CO readings measured at 120 ppm on exhaust with visible black residue on vent pipe. Due to age and safety concerns, recommended immediate discontinuation of furnace operation and provided temporary electric heating while scheduling follow-up for replacement options.

Responded to a no heat emergency for a 20-year-old Amana LP furnace that was blowing cold air and running constantly. Discovered tripped rollout switch. Performed thorough inspection of heat exchanger but could not definitively locate compromise despite checking through blower access and top of unit. CO readings measured at 120 ppm on exhaust with visible black residue on vent pipe. Due to age and safety concerns, recommended immediate discontinuation of furnace operation and provided temporary electric heating while scheduling follow-up for replacement options. Responded to a no heat emergency for a 20-year-old Amana LP furnace that was blowing cold air and running constantly. Discovered tripped rollout switch. Performed thorough inspection of heat exchanger but could not definitively locate compromise despite checking through blower access and top of unit. CO readings measured at 120 ppm on exhaust with visible black residue on vent pipe. Due to age and safety concerns, recommended immediate discontinuation of furnace operation and provided temporary electric heating while scheduling follow-up for replacement options.

Doug T.

Doug T. Job Checkin

Responded to customer call regarding shower malfunction. Upon inspection, found the shower arm had broken off inside the wall where it connects to PEX piping, resulting in active water leakage. Removed damaged components, including the broken eared ell fitting. Completed necessary repiping work and installed new shower head, restoring proper functionality to the shower system.

Responded to customer call regarding shower malfunction. Upon inspection, found the shower arm had broken off inside the wall where it connects to PEX piping, resulting in active water leakage. Removed damaged components, including the broken eared ell fitting. Completed necessary repiping work and installed new shower head, restoring proper functionality to the shower system.